250 kW inverter

Download the MPS-250 datasheet by entering your info below


PARALLELABLE 250 KW UTILITY GRADE AND MICROGRID ENERGY STORAGE INVERTER

250 kW Inverter for Behind-the-Meter Energy Storage

For 480 VAC class grid-connected energy storage applications,  Dynapower offers the patent-pending  MPS-250, a 250 kW inverter from the Micro Power Systems™ (MPS) family of behind the meter, four-quadrant, energy storage inverters.

Dynapower’s flexible and modular patent-pending MPS-250 optimizes the transfer of energy between a DC energy storage system and a three-phase grid. The MPS provides power conditioning (voltage and frequency support), VAR support, and Standby UPS capabilities for intermittent loads and renewable generation. Systems are available in indoor and outdoor configurations. Multiple units can be paralleled in grid forming mode for microgrid applications.

The patent-pending MPS-250 integrates controls and a full complement of switchgear and protection including an AC circuit breaker, AC contractors, AC and DC Fusing, DC load break contactors, and a DC manual isolation switch into a single, heavy duty industrial enclosure. This offers end users and energy storage integrators a cost advantage when compared to non-integrated systems that require additional add-on protection.

ENERGY STORAGE APPLICATIONS

KEY FEATURES

  • Low Acoustic Footprint
  • Parallel Operation in Grid Forming Mode
  • Integrated AC Breaker with Shunt Trip
  • Integrated DC Disconnect
  • Integrated DC Input Fuses
  • Cloud-based remote monitoring

KEY TECHNOLOGY

Dynamic Transfer™ — Dynapower’s proprietary patent pending Dynamic Transfer algorithm monitors the grid stability, and upon detecting a grid disturbance will disconnect from the grid connection and transition to stand-alone mode on the load connection. The transition is seamless to the critical loads and supports 100% phase imbalance in UF mode.


Download the Dynamic Transfer Functional Overview by entering your info below


TWO MODES OF OPERATION
The patent-pending MPS-250 provides two modes of operation — Grid-Tied (PQ-mode) and Stand-Alone (UF mode). In the Grid-Tied mode, the patent-pending MPS-250 controls the AC output real power (P) and reactive power (Q). In Stand-Alone mode, the system controls the AC output voltage (U) and frequency (F). The system can be started in either mode and the transfer between modes is done dynamically. Advanced controls schemes for multi-unit and microgrid applications are available.

SYSTEM CONTROL
Dynapower’s state of the art control and monitoring platform provides operators with both local and remote operation of the system. In the remote operating mode, a communication link provides autonomous operator control via Ethernet, RS232, or RS485. For local control, Dynapower provides an Operator Interface Terminal (OIT) for error set commands and full system display status.

COMPREHENSIVE SYSTEM MONITORING
The patent-pending MPS-250 provides full system status information including AC output real & reactive power, AC output voltage & frequency and DC battery voltage and DC current readings to the remote operator through feedback signals or through the communication link (via an RTU or PLC). An on-board monitoring system captures error history and grid fault data. System operating information is displayed on the OIT in both local and remote modes of operation.

FAULTS
AC Over Voltage, AC Under Voltage, AC Under Frequency, AC Over Frequency, AC Overload, Over-temperature, DC Over Voltage, DC Over Current, Ground Fault

STANDARDS COMPLIANCE
IEEE 1547, UL 1741 SA, UL Listing

SAFETY FEATURES
Anti-islanding with UL compliant trip points

DC Voltage
350 – 600 VDC
Max DC Current
770 A
DC Voltage Ripple
<1%

AC Line Voltage
480 VAC 3 Phase, +10%, -12%
AC Line Frequency
60 Hz (57 – 60.5 Hz) Field Settable
Continuous AC Current
301 A RMS
Overload AC Current
320 A RMS
Continuous AC Power
250 kW
Overload AC Power
300 kW
Power Factor
0 – 1.0 Leading or Lagging
Current Harmonics
IEEE 1547 Compliant, <5% TDD
Peak Efficiency
96.0%

Operating Temp
-25 — 50°C,  De-rated from 45 to 50°C
Cooling
Forced Air Cooled
Rated Max Elevation
1,000 Meters Full Power;
Up to 3,000 Meters With Derating
Enclosure
UL 3R (Outdoor)
Dimensions (HxWxD)
79” x 41” x 41”
Weight
3,500 lbs

Remote Communications
ModBus TCP

Remote Monitoring
DynaCloudTM – Real time monitoring with automated alerts and data logging


Download the MPS-250 datasheet by entering your info below